INCIDENTS: MAIB releases report on Queen Mary 2 explosion

The UK Marine Accident Investigation Branch (MAIB) has released the result of its investigations into a failure of a capacitor, part of the diesel-electric propulsion system of the cruise ship ‘Queen Mary 2’.

The MAIB feels that there are lessons that the industry should learn from this incident, which resulted in an explosion onboard,so has asked for our help in promulgating the information.

At 0425 on 23 September 2010, as the passenger liner Queen Mary 2 (QM2) was approaching Barcelona, a loud explosion was heard from the direction of the aft main switchboard (MSB) room. Within a few seconds, all four of the podded propulsion motors shut down. A few seconds later, the vessel suffered an electrical blackout. Thick black smoke was seen to be coming from the aft MSB room. Fortunately, the vessel was clear of navigational hazards and no one was injured.

By 0439, the crew had confirmed that the explosion had taken place in the aft harmonic filter (HF) which was situated in a compartment next to the aft MSB room. After establishing with thermal imaging cameras that there were no hot spots, they ventilated the area and isolated the aft HF and MSB from the rest of the 11000 volt electrical network. The crew were able to restore some electrical power supplies and, by 0523,QM2 was underway using two propulsion motors powered from the forward MSB. Subsequent inspection of the aft HF revealed that one of its capacitors had failed catastrophically due to internal over-pressure and another had developed a severe bulge.

The vessel had a history of HF capacitor failures, at an average rate of one per year. Although the exact cause of the capacitor failures could not be determined, it was concluded that capacitor degradation was probably caused by a combination of transient high voltage spikes due to frequent switching operations and occasional network over-voltage fluctuations. The capacitor deterioration had not been detected, and because there were no internal fuses or pressure relief devices, it had continued until the capacitor casing failed catastrophically.

Although the aft HF circuit breaker disconnected the HF from the rest of the electrical network to isolate the electrical fault, the disruption was likely to have caused electrical instability in the electrical network which led to the loss of propulsion and blackout. The vessel’s alarm logs were found to contain early warnings about the impending failure approximately 36 minutes before the accident. However, as the vessel’s alarm systems regularly logged more than one alarm every minute, this information was not seen and could not be acted upon.

The only protection against catastrophic failure of the capacitors was a current imbalance detection system. It consisted of a current transformer which was connected to the capacitor circuit. Under normal conditions, little or no current should have flowed through the transformer. When a capacitor degraded, the current flow across the circuit became unbalanced and induced a current in the transformer’s secondary winding. The system was set to give an alarm when the imbalance reached 400mA and to trip at 800mA.After the accident, the transformer’s windings were found to have failed. There had not been any alarms on this part of the system for several years and it was likely that the imbalance detection system had not worked for some time.

This caused the alarm display to read 0mA giving a false indication that the capacitors were in good condition. Although detection of an unbalanced current was the only protection system for the harmonic filters, it had no backup and did not fail safe. Routine tests of the system were by the secondary current injection method, and by-passed the transformer.

Source: http://www.motorship.com/news101/maib-reports-on-qm2-explosion

About these ads

Leave a comment

Filed under Clipping

Leave a Reply

Fill in your details below or click an icon to log in:

WordPress.com Logo

You are commenting using your WordPress.com account. Log Out / Change )

Twitter picture

You are commenting using your Twitter account. Log Out / Change )

Facebook photo

You are commenting using your Facebook account. Log Out / Change )

Google+ photo

You are commenting using your Google+ account. Log Out / Change )

Connecting to %s